Applications
Directly buried or installed in ducts for 600V secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation.
Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation."
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction."
• Secondary URD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854 available upon request.
Ampacity
90°C conductor temperature, 20°C ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Size
|
Stranding |
Insulation
|
Approximate
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|
Clemson |
Size AWG/MCM N/A 2 |
Stranding N/A 7 |
Insulation Thickness (mils) N/A 60 |
Approximate O.D. (inches) N/A 0.403 |
Weight LBS/MFT N/A 93 |
Ampacity 90ºC Direct Burial (amps) N/A 155 |
Ampacity 90ºC In Duct (amps) N/A 115 |
Sewanee |
Size AWG/MCM N/A 750 |
Stranding N/A 61 |
Insulation Thickness (mils) N/A 110 |
Approximate O.D. (inches) N/A 1.188 |
Weight LBS/MFT N/A 855 |
Ampacity 90ºC Direct Burial (amps) N/A 580 |
Ampacity 90ºC In Duct (amps) N/A 470 |
Furman |
Size AWG/MCM N/A 700 |
Stranding N/A 61 |
Insulation Thickness (mils) N/A 110 |
Approximate O.D. (inches) N/A 1.155 |
Weight LBS/MFT N/A 804 |
Ampacity 90ºC Direct Burial (amps) N/A 550 |
Ampacity 90ºC In Duct (amps) N/A 440 |
Duke |
Size AWG/MCM N/A 600 |
Stranding N/A 61 |
Insulation Thickness (mils) N/A 110 |
Approximate O.D. (inches) N/A 1.086 |
Weight LBS/MFT N/A 701 |
Ampacity 90ºC Direct Burial (amps) N/A 510 |
Ampacity 90ºC In Duct (amps) N/A 410 |
Mercer |
Size AWG/MCM N/A 4 |
Stranding N/A 7 |
Insulation Thickness (mils) N/A 60 |
Approximate O.D. (inches) N/A 0.345 |
Weight LBS/MFT N/A 64 |
Ampacity 90ºC Direct Burial (amps) N/A 120 |
Ampacity 90ºC In Duct (amps) N/A 85 |
Emory |
Size AWG/MCM N/A 500 |
Stranding N/A 37 |
Insulation Thickness (mils) N/A 95 |
Approximate O.D. (inches) N/A 0.979 |
Weight LBS/MFT N/A 579 |
Ampacity 90ºC Direct Burial (amps) N/A 465 |
Ampacity 90ºC In Duct (amps) N/A 370 |
Princeton |
Size AWG/MCM N/A 6 |
Stranding N/A 7 |
Insulation Thickness (mils) N/A 60 |
Approximate O.D. (inches) N/A 0.298 |
Weight LBS/MFT N/A 45 |
Ampacity 90ºC Direct Burial (amps) N/A 90 |
Ampacity 90ºC In Duct (amps) N/A 65 |
Rutgers |
Size AWG/MCM N/A 350 |
Stranding N/A 37 |
Insulation Thickness (mils) N/A 95 |
Approximate O.D. (inches) N/A 0.851 |
Weight LBS/MFT N/A 423 |
Ampacity 90ºC Direct Burial (amps) N/A 385 |
Ampacity 90ºC In Duct (amps) N/A 305 |
Gonzaga |
Size AWG/MCM N/A 300 |
Stranding N/A 37 |
Insulation Thickness (mils) N/A 95 |
Approximate O.D. (inches) N/A 0.801 |
Weight LBS/MFT N/A 371 |
Ampacity 90ºC Direct Burial (amps) N/A 355 |
Ampacity 90ºC In Duct (amps) N/A 280 |
Hofstra |
Size AWG/MCM N/A 250 |
Stranding N/A 37 |
Insulation Thickness (mils) N/A 95 |
Approximate O.D. (inches) N/A 0.748 |
Weight LBS/MFT N/A 317 |
Ampacity 90ºC Direct Burial (amps) N/A 320 |
Ampacity 90ºC In Duct (amps) N/A 250 |
Beloit |
Size AWG/MCM N/A 4/0 |
Stranding N/A 19 |
Insulation Thickness (mils) N/A 80 |
Approximate O.D. (inches) N/A 0.672 |
Weight LBS/MFT N/A 265 |
Ampacity 90ºC Direct Burial (amps) N/A 290 |
Ampacity 90ºC In Duct (amps) N/A 225 |
Tufts |
Size AWG/MCM N/A 3/0 |
Stranding N/A 19 |
Insulation Thickness (mils) N/A 80 |
Approximate O.D. (inches) N/A 0.616 |
Weight LBS/MFT N/A 217 |
Ampacity 90ºC Direct Burial (amps) N/A 250 |
Ampacity 90ºC In Duct (amps) N/A 195 |
Yale |
Size AWG/MCM N/A 2/0 |
Stranding N/A 19 |
Insulation Thickness (mils) N/A 80 |
Approximate O.D. (inches) N/A 0.566 |
Weight LBS/MFT N/A 179 |
Ampacity 90ºC Direct Burial (amps) N/A 225 |
Ampacity 90ºC In Duct (amps) N/A 170 |
Kenyon |
Size AWG/MCM N/A 1 |
Stranding N/A 19 |
Insulation Thickness (mils) N/A 80 |
Approximate O.D. (inches) N/A 0.522 |
Weight LBS/MFT N/A 148 |
Ampacity 90ºC Direct Burial (amps) N/A 200 |
Ampacity 90ºC In Duct (amps) N/A 150 |
Harvard |
Size AWG/MCM N/A 1/0 |
Stranding N/A 19 |
Insulation Thickness (mils) N/A 80 |
Approximate O.D. (inches) N/A 0.482 |
Weight LBS/MFT N/A 122 |
Ampacity 90ºC Direct Burial (amps) N/A 175 |
Ampacity 90ºC In Duct (amps) N/A 130 |
Fordham |
Size AWG/MCM N/A 1000 |
Stranding N/A 61 |
Insulation Thickness (mils) N/A 110 |
Approximate O.D. (inches) N/A 1.337 |
Weight LBS/MFT N/A 1109 |
Ampacity 90ºC Direct Burial (amps) N/A 670 |
Ampacity 90ºC In Duct (amps) N/A 545 |