600 V 1350 Aluminum URD Cable – Quadruplex (Type USE-2)
(14)Applications
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.
Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
• Secondary UD quadruplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854
Options
- Cable in Duct (CIC)
- Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
quadruplex URD.jpg
600 V 1350 Aluminum URD Cable – Triplex (Type USE-2)
(17)Applications
Directly buried or installed inducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
• Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854
Options
- Cable in Duct (CIC)
- Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
600 V 8000 Aluminum URD Cable – Triplex (Type USE-2)
Applications
Used for secondary distribution and underground service entrance at 600 V or less, rated 90°C dry or wet, sunlight resistant, and can be direct buried or pulled into raceway (conduit). This cable is designed and manufactured for use in accordance with the National Electrical Code (NEC).
Construction
Conductor:
Compact stranded or compact Single Input Wire (SIW) ACM aluminum (8000 series alloy).
Insulation:
Flame-retardant and sunlight resistant Cross-Linked Polyethylene (XLPE).
Assembly:
Twisted assembly of 2 insulated phase conductors and 1 insulated neutral conductor.
Identification:
Phase Conductors: Black with phase identification (“Phase A”, “Phase B”)
Neutral Conductor: Black with three yellow longitudinal stripes
Features and Markings
- Rated 90 ºC wet or dry
- UL Type RHH/RHW-2
- UL Type USE-2 for direct burial
- Sunlight resistant and marked “SUN RES”
- Deformation-resistant at high temperatures
- Excellent moisture resistance, exceeds UL 44
- Stable electrical properties over a broad temperature range
- Excellent resistance to crush and compression cuts
- Resistant to most oils and chemicals
Standards
These cables are manufactured and tested to meet or exceed the following standards:
- ASTM B800 - 8000 Series Aluminum Alloy Wire for Electrical Purposes - Annealed and Intermediate Tempers
- ASTM B801 - Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
- ASTM B836 - Compact Round Stranded Aluminum Conductors Using Single Input Wire Construction
- UL 44 – Thermoset-Insulated Wire and Cable (UL Type RHH/RHW-2)
- UL 854 – Service-Entrance Cables (UL Type USE-2)
- NFPA 70 – National Electrical Code (NEC)
- ICEA S-95-658/NEMA WC70 – Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Listings and Certifications
- UL listed as Type RHH / RHW-2, USE-2
Notes:
- Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
- Cables are manufactured, tested and marked to meet or exceed the requirements in UL44 for UL Type RHH/RHW-2, and UL 854 for UL Type USE-2.
Packaging:
- Material cut to length and shipped on non-returnable wood reels.
UPDATED: 5/2/2023 triplex URD.jpg
600 V 1350 Aluminum URD Cable – Duplex (Type USE-2)
(4)Applications
Directly buried or installed in ducts for 600V secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation.
Standards
Secondary URD duplex conductor 600V cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation."
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction."
• Secondary URD duplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854 available upon request.
Ampacity
90°C conductor temperature, 20°C ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
duplex URD.jpg
600 V 1350 Aluminum URD Cable – Single (Type USE-2)
(16)Applications
Directly buried or installed in ducts for 600V secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation.
Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation."
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction."
• Secondary URD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854 available upon request.
Ampacity
90°C conductor temperature, 20°C ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.