Applications
Directly buried or installed in ducts for 600V secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation.
Standards
Secondary URD duplex conductor 600V cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation."
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction."
• Secondary URD duplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854 available upon request.
Ampacity
90°C conductor temperature, 20°C ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Phase
|
Phase
|
Phase
|
Neutral
|
Neutral
|
Neutral
|
Single
|
Approximate
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|---|
Bard |
Phase Conductor Size AWG/KCMIL N/A 8 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Insulation Thickness (mils) N/A 60 |
Neutral Size AWG/MCM N/A 8 |
Neutral Stranding N/A 7 |
Neutral Insulation Thickness (mils) N/A 60 |
Single Phase Conductor (inches) N/A 0.262 |
Approximate O.D. (inches) N/A 0.524 |
Weight LBS/MFT N/A 76 |
Ampacity 90ºC Direct Burial (amps) N/A 70 |
Ampacity 90ºC In Duct (amps) N/A 70 |
Claflin |
Phase Conductor Size AWG/KCMIL N/A 6 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Insulation Thickness (mils) N/A 60 |
Neutral Size AWG/MCM N/A 6 |
Neutral Stranding N/A 7 |
Neutral Insulation Thickness (mils) N/A 60 |
Single Phase Conductor (inches) N/A 0.299 |
Approximate O.D. (inches) N/A 0.596 |
Weight LBS/MFT N/A 91 |
Ampacity 90ºC Direct Burial (amps) N/A 95 |
Ampacity 90ºC In Duct (amps) N/A 70 |
Delgado |
Phase Conductor Size AWG/KCMIL N/A 4 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Insulation Thickness (mils) N/A 60 |
Neutral Size AWG/MCM N/A 4 |
Neutral Stranding N/A 7 |
Neutral Insulation Thickness (mils) N/A 60 |
Single Phase Conductor (inches) N/A 0.345 |
Approximate O.D. (inches) N/A 0.69 |
Weight LBS/MFT N/A 129 |
Ampacity 90ºC Direct Burial (amps) N/A 125 |
Ampacity 90ºC In Duct (amps) N/A 90 |
Everett |
Phase Conductor Size AWG/KCMIL N/A 2 |
Phase Conductor Stranding N/A 7 |
Phase Conductor Insulation Thickness (mils) N/A 60 |
Neutral Size AWG/MCM N/A 2 |
Neutral Stranding N/A 7 |
Neutral Insulation Thickness (mils) N/A 60 |
Single Phase Conductor (inches) N/A 0.403 |
Approximate O.D. (inches) N/A 0.806 |
Weight LBS/MFT N/A 189 |
Ampacity 90ºC Direct Burial (amps) N/A 187 |
Ampacity 90ºC In Duct (amps) N/A 100 |