Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows: Class AA For bare conductors usually used in overhead lines. Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required. Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available. Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.

Specifications
AAC bare conductors meet or exceed the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
• B-231 Aluminum Conductors, Concentric-Lay-Stranded
• B-400 Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors

Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
51 - 56 of 56 | Results Per Page | View |
1 2 3 

Item #

Size
AWG
KCMIL

No.
of
Wires

CLASS

Diameter
Individual
Wire
(inches)

Diameter
Complete
Cable
(O.D.)
(Inches)

Cross
Sectional
Area
(sq.inches)

Weight
(lbs/MFT)

Rated
Breaking
Strength
(lbs)

Resistance
DC
20 ºC
Per MFT
(ohm)

Resistance
AC
75 ºC
per MFT
(ohm)

Rating
(Amps)

Sort by
N/A 2/0 N/A 7 N/A A AA N/A 0.1379 N/A 0.414 N/A 0.1045 N/A 124.9 N/A 2510 N/A 0.130 N/A 0.159 N/A 286
N/A 1/0 N/A 7 N/A A AA N/A 0.1228 N/A 0.368 N/A 0.0829 N/A 78.5 N/A 1990 N/A 0.164 N/A 0.202 N/A 247
N/A 1 N/A 7 N/A A AA N/A 0.1093 N/A 0.328 N/A 0.0657 N/A 99.1 N/A 1640 N/A 0.207 N/A 0.252 N/A 214
N/A 2 N/A 7 N/A A AA N/A 0.0974 N/A 0.292 N/A 0.0521 N/A 62.3 N/A 1350 N/A 0.260 N/A 0.318 N/A 185
N/A 4 N/A 7 N/A A N/A 0.0772 N/A 0.232 N/A 0.0328 N/A 39.2 N/A 881 N/A 0.414 N/A 0.506 N/A 138
N/A 6 N/A 7 N/A A N/A 0.0612 N/A 0.184 N/A 0.0206 N/A 24.6 N/A 563 N/A 0.658 N/A 0.805 N/A 103
51 - 56 of 56 | Results Per Page | View |