Applications
To supply 120V aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600V or lower at a conductor temperature of 75°C maximum.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand AAC neutral messenger.
Standards
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
• Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, Latest edition.
Item # |
Phase
|
Phase
|
Phase
|
Bare
|
Bare
|
Bare
|
Weight
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|
Spaniel |
Phase Conductor Size/AWG N/A 4 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 4 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 881 |
Weight Per MFT XLP (lbs/MFT) N/A 100.5 |
Weight Per MFT Poly (lbs/MFT) N/A 95.4 |
Ampacity XLP (Amps) N/A 115 |
Ampacity Poly (Amps) N/A 90 |
Doberman |
Phase Conductor Size/AWG N/A 2 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 2 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1350 |
Weight Per MFT XLP (lbs/MFT) N/A 152.7 |
Weight Per MFT Poly (lbs/MFT) N/A 145.7 |
Ampacity XLP (Amps) N/A 150 |
Ampacity Poly (Amps) N/A 120 |
Malemute |
Phase Conductor Size/AWG N/A 1/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness (mls) N/A 60 |
Bare Neutral Messenger Size/AWG N/A 1/0 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1990 |
Weight Per MFT XLP (lbs/MFT) N/A 242.6 |
Weight Per MFT Poly (lbs/MFT) N/A 234.2 |
Ampacity XLP (Amps) N/A 205 |
Ampacity Poly (Amps) N/A 160 |
Pekingese |
Phase Conductor Size/AWG N/A 6 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 6 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 563 |
Weight Per MFT XLP (lbs/MFT) N/A 63.5 |
Weight Per MFT Poly (lbs/MFT) N/A 61.7 |
Ampacity XLP (Amps) N/A 85 |
Ampacity Poly (Amps) N/A 70 |
Collie |
Phase Conductor Size/AWG N/A 6 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 6 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 563 |
Weight Per MFT XLP (lbs/MFT) N/A 66.8 |
Weight Per MFT Poly (lbs/MFT) N/A 63.1 |
Ampacity XLP (Amps) N/A 85 |
Ampacity Poly (Amps) N/A 70 |
Dachshund |
Phase Conductor Size/AWG N/A 4 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 4 |
Bare Neutral Messenger Stranding N/A 7/w |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 881 |
Weight Per MFT XLP (lbs/MFT) N/A 95.5 |
Weight Per MFT Poly (lbs/MFT) N/A 93.4 |
Ampacity XLP (Amps) N/A 115 |