Applications
To supply 120V aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600V or lower at a conductor temperature of 75°C maximum.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand ACSR neutral messenger.
Standards
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
• Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, Latest edition.
Item # |
Phase
|
Phase
|
Phase
|
Bare
|
Bare
|
Bare
|
Weight
|
Weight
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|
Eskimo |
Phase Conductor Size/AWG N/A 4 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 4 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1860 |
Weight Per MFT XLP (lbs/MFT) N/A 113.7 |
Weight Per MFT Poly (lbs/MFT) N/A 111.6 |
Ampacity XLP (Amps) N/A 115 |
Ampacity Poly (Amps) N/A 90 |
Terrier |
Phase Conductor Size/AWG N/A 4 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 4 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1860 |
Weight Per MFT XLP (lbs/MFT) N/A 118.7 |
Weight Per MFT Poly (lbs/MFT) N/A 113.6 |
Ampacity XLP (Amps) N/A 115 |
Ampacity Poly (Amps) N/A 90 |
Chow |
Phase Conductor Size/AWG N/A 2 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 2 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 2850 |
Weight Per MFT XLP (lbs/MFT) N/A 181.7 |
Weight Per MFT Poly (lbs/MFT) N/A 174.7 |
Ampacity XLP (Amps) N/A 150 |
Ampacity Poly (Amps) N/A 120 |
Bull |
Phase Conductor Size/AWG N/A 1/0 |
Phase Conductor Stranding N/A 19/w |
Phase Conductor Insulation Thickness (mls) N/A 60 |
Bare Neutral Messenger Size/AWG N/A 1/0 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 4380 |
Weight Per MFT XLP (lbs/MFT) N/A 288.7 |
Weight Per MFT Poly (lbs/MFT) N/A 280.3 |
Ampacity XLP (Amps) N/A 205 |
Ampacity Poly (Amps) N/A 160 |
Setter |
Phase Conductor Size/AWG N/A 6 |
Phase Conductor Stranding N/A Solid |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 6 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1190 |
Weight Per MFT XLP (lbs/MFT) N/A 75.0 |
Weight Per MFT Poly (lbs/MFT) N/A 73.2 |
Ampacity XLP (Amps) N/A 85 |
Ampacity Poly (Amps) N/A 70 |
Shepherd |
Phase Conductor Size/AWG N/A 6 |
Phase Conductor Stranding N/A 7/w |
Phase Conductor Insulation Thickness (mls) N/A 45 |
Bare Neutral Messenger Size/AWG N/A 6 |
Bare Neutral Messenger Stranding N/A 6/1 |
Bare Neutral Messenger Breaking Strength (lbs/MFT) N/A 1190 |
Weight Per MFT XLP (lbs/MFT) N/A 78.3 |
Weight Per MFT Poly (lbs/MFT) N/A 74.6 |
Ampacity XLP (Amps) N/A 85 |
Ampacity Poly (Amps) N/A 70 |