Applications 
To supply 120V aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600V or lower at a conductor temperature of 75°C maximum.

Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand ACSR neutral messenger.

Standards

• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
• Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, Latest edition.

 

 

1 - 6 of 6 | Results Per Page | View |
1 

Item #

Phase
Conductor
Size/AWG

Phase
Conductor
Stranding

Phase
Conductor
Insulation
Thickness
(mls)

Bare
Neutral
Messenger
Size/AWG

Bare
Neutral
Messenger
Stranding

Bare
Neutral
Messenger
Breaking
Strength
(lbs/MFT)

Weight
Per
MFT
XLP
(lbs/MFT)

Weight
Per
MFT
Poly
(lbs/MFT)

Ampacity
XLP
(Amps)

Ampacity
Poly
(Amps)

Sort by
N/A 1/0 N/A 19/w N/A 60 N/A 1/0 N/A 6/1 N/A 4380 N/A 288.7 N/A 280.3 N/A 205 N/A 160
N/A 2 N/A 7/w N/A 45 N/A 2 N/A 6/1 N/A 2850 N/A 181.7 N/A 174.7 N/A 150 N/A 120
N/A 4 N/A Solid N/A 45 N/A 4 N/A 6/1 N/A 1860 N/A 113.7 N/A 111.6 N/A 115 N/A 90
N/A 6 N/A Solid N/A 45 N/A 6 N/A 6/1 N/A 1190 N/A 75.0 N/A 73.2 N/A 85 N/A 70
N/A 6 N/A 7/w N/A 45 N/A 6 N/A 6/1 N/A 1190 N/A 78.3 N/A 74.6 N/A 85 N/A 70
N/A 4 N/A 7/w N/A 45 N/A 4 N/A 6/1 N/A 1860 N/A 118.7 N/A 113.6 N/A 115 N/A 90
1 - 6 of 6 | Results Per Page | View |