Applications
Classic Wire Type MC Cable is primarily used for services, feeders, and branch circuits as specified in the 2011 National Electric Code. Type MC cable with Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Used for power and lighting indoors, exposed or concealed, in cable tray where identified for such use; in a raceway, or in dry locations and embedded in plaster or against other masonry. Voltage rating for XHHW-2 conductors is 600V.
Construction
Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable. XLPE insulated XHHW-2 conductors are twisted with a bare conductor. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Rated 90°C wet or dry and is flame and sunlight resistant.
Specifications
Classic Wire Type MC cable with Type XHHW-2 conductors are manufactured and tested in accordance with the latest revisions of:
- UL 44 for Thermoset-Insulated Wires and Cables
- UL 83 for Thermoplastic-Insulated Wires and Cables
- UL 1479 Standard for Fire Tests of Through-Penetration Firestops.
- UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
- UL 1569 for Metal-Clad Cables.
- IEEE 1202 - Flame Testing of Cables for Use in Cable Tray, in Industrial and Commercial Occupancies (70,000 BTU/hr).
- ICEA T-29-520 - Vertical Cable Tray Flame Tests (210,000 Btu/hr).
- ICEA S-66-524 and requirements of the National Electric Code
- ICEA S-95-658 (NEMA WC 70) construction requirements
- Federal Specification J-C-30B
- UL Listed.
Color Code
Three Phase Conductors (3): Black, red, white
Four Phase Conductors (4): Black, red, blue, white
Grounding Conductor (1): Bare
Other colors and stripes available by special order.
For Special Order
- The entire assembly can be covered with a PVC or CPE outer jacket (black or color). Jacketed MC Cable may be used in wet locations, either direct burial, in underground conduit, or overhead.
- Halogen free jackets are available upon request
- A black jacket (on individual conductors) with color stripes can be requested.
- Bare Ground conductor available upon request.
- For sizes not listed above please contact sales.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Cable
|
Phase
|
Number
|
Diameter
|
Thickness
|
Size
|
Diameter
|
Thickness
|
Cabling
|
Overall
|
AL
|
Cable
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
A6-03MC6 |
Cable Description N/A 6-6-6+6 |
Phase Conductor Size AWG/KCMIL N/A 6 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 169 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 626 |
Overall Diameter of Cable Over Armour (mils) N/A 900 |
AL Weight (lb/mft) N/A 206 |
Cable Weight (lb/mft) N/A 271 |
A4-03MC6 |
Cable Description N/A 4-4-4+6 |
Phase Conductor Size AWG/KCMIL N/A 4 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 213 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 720 |
Overall Diameter of Cable Over Armour (mils) N/A 994 |
AL Weight (lb/mft) N/A 264 |
Cable Weight (lb/mft) N/A 339 |
A2-03MC6 |
Cable Description N/A 2-2-2+6 |
Phase Conductor Size AWG/KCMIL N/A 2 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 268 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 843 |
Overall Diameter of Cable Over Armour (mils) N/A 1116 |
AL Weight (lb/mft) N/A 350 |
Cable Weight (lb/mft) N/A 438 |
A6-04MC6 |
Cable Description N/A 6-6-6-6+6 |
Phase Conductor Size AWG/KCMIL N/A 6 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 169 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 701 |
Overall Diameter of Cable Over Armour (mils) N/A 974 |
AL Weight (lb/mft) N/A 242 |
Cable Weight (lb/mft) N/A 322 |
A4-04MC6 |
Cable Description N/A 4-4-4-4+6 |
Phase Conductor Size AWG/KCMIL N/A 4 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 213 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 803 |
Overall Diameter of Cable Over Armour (mils) N/A 1077 |
AL Weight (lb/mft) N/A 315 |
Cable Weight (lb/mft) N/A 409 |
A2-04MC6 |
Cable Description N/A 2-2-2-2+6 |
Phase Conductor Size AWG/KCMIL N/A 2 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 268 |
Thickness of Conductor Insulation (mils) N/A 45 |
Size of Ground Conductor AWG/KCMIL N/A 6 |
Diameter of Ground (mils) N/A 169 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 929 |
Overall Diameter of Cable Over Armour (mils) N/A 1203 |
AL Weight (lb/mft) N/A 425 |
Cable Weight (lb/mft) N/A 535 |
A1-03MC4 |
Cable Description N/A 1-1-1+4 |
Phase Conductor Size AWG/KCMIL N/A 1 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 961 |
Overall Diameter of Cable Over Armour (mils) N/A 1234 |
AL Weight (lb/mft) N/A 431 |
Cable Weight (lb/mft) N/A 548 |
A1/0-03MC4 |
Cable Description N/A 1/0-1/0-1/0+4 |
Phase Conductor Size AWG/KCMIL N/A 1/0 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1028 |
Overall Diameter of Cable Over Armour (mils) N/A 1301 |
AL Weight (lb/mft) N/A 503 |
Cable Weight (lb/mft) N/A 629 |
A2/0-03MC4 |
Cable Description N/A 2/0-2/0-2/0+4 |
Phase Conductor Size AWG/KCMIL N/A 2/0 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1118 |
Overall Diameter of Cable Over Armour (mils) N/A 1392 |
AL Weight (lb/mft) N/A 592 |
Cable Weight (lb/mft) N/A 730 |
A3/0-03MC4 |
Cable Description N/A 3/0-3/0-3/0+4 |
Phase Conductor Size AWG/KCMIL N/A 3/0 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1197 |
Overall Diameter of Cable Over Armour (mils) N/A 1470 |
AL Weight (lb/mft) N/A 700 |
Cable Weight (lb/mft) N/A 850 |
A4/0-03MC2 |
Cable Description N/A 4/0-4/0-4/0+2 |
Phase Conductor Size AWG/KCMIL N/A 4/0 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1346 |
Overall Diameter of Cable Over Armour (mils) N/A 1620 |
AL Weight (lb/mft) N/A 866 |
Cable Weight (lb/mft) N/A 1035 |
A1-04MC4 |
Cable Description N/A 1-1-1-1+4 |
Phase Conductor Size AWG/KCMIL N/A 1 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 299 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1063 |
Overall Diameter of Cable Over Armour (mils) N/A 1337 |
AL Weight (lb/mft) N/A 524 |
Cable Weight (lb/mft) N/A 672 |
A1/0-04MC4 |
Cable Description N/A 1/0-1/0-1/0-1/0+4 |
Phase Conductor Size AWG/KCMIL N/A 1/0 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 336 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1138 |
Overall Diameter of Cable Over Armour (mils) N/A 1411 |
AL Weight (lb/mft) N/A 617 |
Cable Weight (lb/mft) N/A 778 |
A2/0-04MC4 |
Cable Description N/A 2/0-2/0-2/0-2/0+4 |
Phase Conductor Size AWG/KCMIL N/A 2/0 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 376 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1240 |
Overall Diameter of Cable Over Armour (mils) N/A 1514 |
AL Weight (lb/mft) N/A 733 |
Cable Weight (lb/mft) N/A 909 |
A3/0-04MC4 |
Cable Description N/A 3/0-3/0-3/0-3/0+4 |
Phase Conductor Size AWG/KCMIL N/A 3/0 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 421 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 4 |
Diameter of Ground (mils) N/A 213 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1327 |
Overall Diameter of Cable Over Armour (mils) N/A 1600 |
AL Weight (lb/mft) N/A 875 |
Cable Weight (lb/mft) N/A 1066 |
A4/0-04MC2 |
Cable Description N/A 4/0-4/0-4/0-4/0+2 |
Phase Conductor Size AWG/KCMIL N/A 4/0 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 476 |
Thickness of Conductor Insulation (mils) N/A 55 |
Size of Ground Conductor AWG/KCMIL N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1492 |
Overall Diameter of Cable Over Armour (mils) N/A 1816 |
AL Weight (lb/mft) N/A 1134 |
Cable Weight (lb/mft) N/A 1350 |
A250-03MC2 |
Cable Description N/A 250-250-250+2 |
Phase Conductor Size AWG/KCMIL N/A 250 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1461 |
Overall Diameter of Cable Over Armour (mils) N/A 1734 |
AL Weight (lb/mft) N/A 993 |
Cable Weight (lb/mft) N/A 1203 |
A300-03MC2 |
Cable Description N/A 300-300-300+2 |
Phase Conductor Size AWG/KCMIL N/A 300 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1579 |
Overall Diameter of Cable Over Armour (mils) N/A 1902 |
AL Weight (lb/mft) N/A 1201 |
Cable Weight (lb/mft) N/A 1428 |
A350-03MC2 |
Cable Description N/A 350-350-350+2 |
Phase Conductor Size AWG/KCMIL N/A 350 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 2 |
Diameter of Ground (mils) N/A 268 |
Thickness of Ground Insulation (mils) N/A 45 |
Cabling Diameter (mils) N/A 1638 |
Overall Diameter of Cable Over Armour (mils) N/A 1961 |
AL Weight (lb/mft) N/A 1348 |
Cable Weight (lb/mft) N/A 1589 |
A400-03MC1 |
Cable Description N/A 400-400-400+1 |
Phase Conductor Size AWG/KCMIL N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1772 |
Overall Diameter of Cable Over Armour (mils) N/A 2095 |
AL Weight (lb/mft) N/A 1531 |
Cable Weight (lb/mft) N/A 1794 |
A500-03MC1 |
Cable Description N/A 500-500-500+1 |
Phase Conductor Size AWG/KCMIL N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1828 |
Cable Weight (lb/mft) N/A 2116 |
A250-04MC1 |
Cable Description N/A 250-250-250-250+1 |
Phase Conductor Size AWG/KCMIL N/A 250 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 520 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1657 |
Overall Diameter of Cable Over Armour (mils) N/A 1981 |
AL Weight (lb/mft) N/A 1326 |
Cable Weight (lb/mft) N/A 1605 |
A300-04MC1 |
Cable Description N/A 300-300-300-300+1 |
Phase Conductor Size AWG/KCMIL N/A 300 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 571 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1752 |
Overall Diameter of Cable Over Armour (mils) N/A 2076 |
AL Weight (lb/mft) N/A 1525 |
Cable Weight (lb/mft) N/A 1826 |
A350-04MC1/0 |
Cable Description N/A 350-350-350-350+1/0 |
Phase Conductor Size AWG/KCMIL N/A 350 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 614 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1/0 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1862 |
Overall Diameter of Cable Over Armour (mils) N/A 2186 |
AL Weight (lb/mft) N/A 1748 |
Cable Weight (lb/mft) N/A 2070 |
A400-04MC1/0 |
Cable Description N/A 400-400-400-400+1/0 |
Phase Conductor Size AWG/KCMIL N/A 400 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 1/0 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1969 |
Overall Diameter of Cable Over Armour (mils) N/A 2292 |
AL Weight (lb/mft) N/A 1957 |
Cable Weight (lb/mft) N/A 2297 |
A500-04MC2/0 |
Cable Description N/A 500-500-500-500+2/0 |
Phase Conductor Size AWG/KCMIL N/A 500 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 2/0 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2165 |
Overall Diameter of Cable Over Armour (mils) N/A 2489 |
AL Weight (lb/mft) N/A 2382 |
Cable Weight (lb/mft) N/A 2759 |
A500-04MC250 |
Cable Description N/A 500-500-500-500+250 |
Phase Conductor Size AWG/KCMIL N/A 500 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/KCMIL N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2252 |
Overall Diameter of Cable Over Armour (mils) N/A 2576 |
AL Weight (lb/mft) N/A 2506 |
Cable Weight (lb/mft) N/A 2906 |
A600-03MC400 |
Cable Description N/A 600-600-600+400 |
Phase Conductor Size AWG/KCMIL N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2476 |
Cable Weight (lb/mft) N/A 2900 |
A750-03MC1/0 |
Cable Description N/A 750-750-750+1/0 |
Phase Conductor Size AWG/KCMIL N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 1/0 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2616 |
Cable Weight (lb/mft) N/A 3036 |
A600-03MC41 |
Cable Description N/A 600-600-600+1 |
Phase Conductor Size AWG/KCMIL N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2106 |
Overall Diameter of Cable Over Armour (mils) N/A 2430 |
AL Weight (lb/mft) N/A 2144 |
Cable Weight (lb/mft) N/A 2524 |
A600-04MC2/0 |
Cable Description N/A 600-600-600-600+2/0 |
Phase Conductor Size AWG/KCMIL N/A 600 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 2/0 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2417 |
Overall Diameter of Cable Over Armour (mils) N/A 2741 |
AL Weight (lb/mft) N/A 2800 |
Cable Weight (lb/mft) N/A 3299 |
A600-04MC400 |
Cable Description N/A 600-600-600-600+400 |
Phase Conductor Size AWG/KCMIL N/A 600 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2583 |
Overall Diameter of Cable Over Armour (mils) N/A 2906 |
AL Weight (lb/mft) N/A 3077 |
Cable Weight (lb/mft) N/A 3614 |
A750-04MC3/0 |
Cable Description N/A 750-750-750-750+3/0 |
Phase Conductor Size AWG/KCMIL N/A 750 |
Number of Phase Conductors N/A 4 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/KCMIL N/A 3/0 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2650 |
Overall Diameter of Cable Over Armour (mils) N/A 2973 |
AL Weight (lb/mft) N/A 3427 |
Cable Weight (lb/mft) N/A 3979 |