Applications
Directly buried or installed inducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) or parallel if so specified. Black neutrals may be specified if desired.

Standards

Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
• Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854

Options
Cable in Duct (CIC) Abrasion Resistant

Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.

Phase
Conductor
Size/AWG

N/A 1/0

Phase
Conductor
Stranding

N/A 19/w

Phase
Conductor
Insulation
Thickness
(mils)

N/A 80

Neutral
Size
AWG

N/A 2

Neutral
Stranding

N/A 7/w

Neutral
Insulation
Thickness
(mils)

N/A 60

Single
Phase
Conductor
(inches)

N/A .522

Outside
Diameter
(inches)

N/A 1.064

Weight
(lbs/MFT)

N/A 408

Ampacity
Direct
Burial
(amps)

N/A 215

Ampacity
In Duct
(amps)

N/A 160