Applications
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75 ºC maximum for polyethylene Insulation or 90 ºC maximum for crosslinked insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand ACSR Neutral Messenger.
Standards
• B-230 Aluminum Wire 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
• Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, Latest edition.
Phase
|
N/A 336.4 |
Phase
|
N/A 19/w |
Phase
|
N/A 80 |
Bare
|
N/A 336.4 |
Bare
|
N/A 18/1 |
Bare
|
N/A 8680 |
Weight
|
N/A 1209 |
Weight
|
N/A 1167 |
Ampacity
|
N/A 420 |
Ampacity
|
N/A 325 |